SET-UP:
1) Verify all components are properly installed.
2) Set the adjustable timer inside the panel (see Diagram F). This setting is dependent on the fill rate and the configuration of the particular silo. When the point level device first senses material, the over-fill indicator on the front of the panel will illuminate, the horn will sound and the timer delay is activated. When the delay time has elapsed. the orange stroble light will activate and the pinch valve will shut down the line. Adjust the timer delay to the appropriate setting. The timer is adjusted by turning the knob to the appropriate setting. The scale is also adjustable allowing for a wide range of settings. IT THIS SETTING IS NOT PROPERLY DETERMINED AND SET, THE SILO MAY OVER-FILL BEFORE THE VISUAL ALARM AND THE PINCH VALVE ARE ACTIVATED. A DANGEROUS CONDITION LEADING TO PROPERTY DAMAGE AND/OR PERSONAL INJURY OR DEATH MAY RESULT. Record your predetermined timer setting in the following table:
| TYPE OF SETTING |
USER SETTING |
| CONTROL PANEL TIMER |
|
Diagram G
3) Set Pessure setpoints.
a. Establish user pressure setpoints. CONSULT WITH THE MANUFACTURERS OF YOUR WILO AND OTHER DEVICES TO DETERMINE AMOUNT OF PRESSURE YOUR PARTICULAR SILO IS SAFELY ABLE TO WITHSTAND. IF THIS PROCEDURE IS NOT PERFORMED, A DANGEROUS CONDITION LEADING TO PROPERTY DAMAGE AND/OR PERSONAL INJURY OR DEATH MAY RESULT. The default setpoints are indicated in table 2. Record your predetermined user settings in the column provided.
| TYPE OF SETTING |
DEFAULT |
USER SETTINGS |
| Control Panel Setpoint 1 |
0.75 PSI |
|
| Control Panel Setpoint 2 |
1.0 PSI |
|
| Pressure Relief Valve |
1.1 PSI |
|
4) Adjust pressure setpoints as necessary
a. Control Panel Setpoint 1. This setpoint is the Warning Setpoint and will activate the Over Pressure indicator on the front of the panel as well as the horn. This setting has been preset to 0.75 PSI. To adjust, perform the following:
1a) Temporarily connect a verified air pressure source to the barb connection at the bottom of the control panel (this is connected to the "=" port on the Photohelic Gauge.) MAXIMUM ALLOWABLE AIR PRESSURE CONNECTED TO THE PHOTOHELIC GAUGE IS 30 PSI.
2a) Turn the Power Off/On switch to the "ON" position. This will power up the Photohelic Gauge (24 VAC). CAUTION: THIS MUST BE PERFORMED BY QUALIFIED PERSONNEL. THE PANEL WILL BE ENERGIZED. HAZARD OF ELECTRICAL SHOCK IS PRESENT.
3a) When the desired pressure is indicated on the Photohelic Gauge, press and hold the red button labeled "SP1" on the back of the gauge (see Diagram G). The red LED on the back will blink. Continue to hold the button until the LED illuminates solid.
b. Control Panel Setpoint 2. This setpoint is the activation point for the orange strobe light and the Pinch Valve. This setting has been preset to 1.0 PSI. To adjust, perform the following:
1a) Temporarily connect a verified air pressure source to the barb connection at the bottom of the control panel (this is connected to the "+" port on the Photohelic Gauge.) MAXIMUM ALLOWABLE AIR PRESSURE CONNECTED TO THE PHOTOHELIC GAUGE IS 30 PSI.
2a) Turn the Power Off/On switch to the "ON" position. This will power up the Photohelic Gauge (24 VAC). CAUTION: THIS MUST BE PERFORMED BY QUALIFIED PERSONNEL. THE PANEL WILL BE ENERGIZED. HAZARD OF ELECTRICAL SHOCK IS PRESENT.
3a) When the desired pressure is indicated on the Photohelic Gauge, press and hold the red button labeled "SP2" on the back of the gauge (see Diagram G). The red LED on the back will blink. Continue to hold the button until the LED illuminates solid. 1.1
c. Pressure Relief Valve Setpoint. This setting has been preset to 1.4 PSI. (refer to the Pressure Relief Valve I & O Manual for adjustment procedure)
DIAGRAM H
|